Preliminary Feasibility Assessment for High
Efficiency, Low Emission Wood Heating In
Hoonah, Alaska
Prepared on behalf of:
Hoonah School District
Hoonah, AK
Steve Pine, Principal/Superintendent
Prepared by:
Daniel Parrent,
Wood Utilization Specialist
Juneau Economic Development Council
Friday, October 17, 2008
Notice
This Preliminary Feasibility Assessment for High Efficiency, Low Emission Wood Heating was prepared by
Daniel Parrent, Wood Utilization Specialist, Juneau Economic Development Council on behalf of the Hoonah
School District, Hoonah, AK, Steve Pine, Principal/Superintendent. This report does not necessarily represent
the views of the Juneau Economic Development Council (JEDC). JEDC, its Board, employees, contractors,
and subcontractors make no warranty, express or implied, and assume no legal liability for the information in
this report; nor does any party represent that the use of this information will not infringe upon privately owned
rights. This report has not been approved or disapproved by JEDC nor has JEDC passed upon the accuracy
or adequacy of the information in this report.
Funding for this report was provided by USDA Forest Service, Alaska Region,
Office of State and Private Forestry
2
Table of Contents
Abstract
Section 1. Executive Summary
1.1 Goals and Objectives
1.2 Evaluation Criteria, Project Scale, Operating Standards, General Observations
1.3 Assessment Summary and Recommended Actions
1.4 Power Generation and Waste Heat Capture
Section 2. Evaluation Criteria, Implementation, Wood Heating Systems
2.1 Evaluation Criteria
2.2 Successful Implementation
2.3 Classes of Wood Heating Systems
Section 3. The Nature of Wood Fuels
3.1 Wood Fuel Forms and Current Utilization
3.2 Heating Value of Wood
Section 4. Wood Fueled Heating Systems
4.1 Low Efficiency High Emission Cordwood Boilers
4.2 High Efficiency Low Emission Cordwood Boilers
4.3 Bulk Fuel Boiler Systems
Section 5. Selecting the Appropriate System
5.1 Comparative Costs of Fuels
5.2(a) Cost per MMBtu Sensitivity – Cordwood
5.2(b) Cost per MMBtu Sensitivity – Bulk Fuels
5.3 Determining Demand
5.4 Summary of Findings
Section 6. Economic Feasibility of Cordwood Systems
6.1 Initial Investment Cost Estimates
6.2 Operating Parameters of HELE Cordwood Boilers
6.3 Hypothetical OM&R Cost Estimates
6.4 Calculation of Financial Metrics
6.5 Simple Payback Period for Small and Large HELE Cordwood Boilers
6.6 Present Value, Net Present Value and Internal Rate of Return Values for Multiple
HELE Cordwood Boilers
6.7 The Case for Fuel Purchase Planning and Fuel Storage
6.8 Life Cycle Cost Analysis
Section 7. Economic Feasibility of Bulk Fuel Systems
7.1 Capital Cost Components
7.2 Generic OM&R Cost Allowances
7.3 Calculation of Financial Metrics
7.4 Simple Payback Period for Generic Bulk Fuel Boilers
7.5 Present Value, Net Present Value and Internal Rate of Return Values for Bulk Fuel Boilers
Section 8. Conclusions
8.1 Cordwood Systems
8.2 Bulk Fuel Systems
References and Resources
3
Appendix A AWEDTG Evaluation Criteria
Appendix B Recoverable Heating Value Determination
Appendix C List of Abbreviations and Acronyms
Appendix D Wood Fuel Properties
Appendix E Financial Metrics
Appendix F Operational Parameters of HELE Cordwood Boilers
Appendix G Calculation of Present Value, Net Present Value and Internal Rate of Return
Appendix H Garn Boiler Specifications
List of Tables and Figures
Table 4-1 HELE Cordwood Boiler Suppliers
Table 4-2 Emissions from Wood Heating Appliances
Table 4-3 Bulk Fuel Boiler System Vendors
Table 4-4 Bulk Fuel Boilers in Alaska
Table 5-1 Comparative Cost of Fuel Oil vs. Wood Fuels
Figure 5-1 Effect of Hemlock Cordwood (MC30) Cost on Cost of Delivered Heat
Figure 5-2 Effect of Hemlock Bulk Fuel (MC50) Cost on Cost of Delivered Heat
Table 5-2 Reported Annual Fuel Oil Consumption, Hoonah School and Gym/pool
Table 5-3 Estimate of Heat Required in Coldest 24 Hr Period
Table 5-4 Estimate of Total Wood Consumption, Comparative Costs and Potential Savings
Table 6-1 Initial Investment Cost Scenarios for Hypothetical Cordwood Systems
Table 6-2 Labor/Cost Estimates for HELE Cordwood Systems
Table 6-3 Summary of Total Annual OM&R Cost Estimates
Table 6-4 Simple Payback Period Analysis for HELE Cordwood Boilers
Table 6-5 PV, NPV and IRR Values for HELE Cordwood Boilers
Table 7-1 Initial Investment Cost Components for Bulk Fuel Systems
Table 7-2 Darby, MT Public School Wood Chip Boiler Costs
Table 7-3 Characteristics of Biomass Boiler Projects
Table 7-4 Cost Breakdown for the Least Expensive Wood Chip Boiler System Installed in a New Free-
Standing Building
Table 7-5 Total OM&R Cost Allowances for a Bulk Fuel System
Table 7-6 Simple Payback Period Analysis for Bulk Fuel Heating Systems
Table 7-7 PV, NPV and IRR Values for Bulk Fuel Systems
4
Key words: HELE, LEHE, bulk fuel, cordwood
ABSTRACT
The potential for heating the Hoonah School in Hoonah, AK with high efficiency, low emission
(HELE) wood-fired boilers is evaluated for the Hoonah School District, Hoonah, AK.
SECTION 1. EXECUTIVE SUMMARY
1.1 Goals and Objectives
• Inspect the Hoonah School and gym/pool facility and physical site in Hoonah as potential
candidates for heating with wood
• Evaluate the suitability of the facility(s) and site(s) for siting a wood-fired boiler
• Assess the type(s) and availability of wood fuel(s)
• Size and estimate the capital costs of suitable wood-fired system(s)
• Estimate the annual operation and maintenance costs of a wood-fired system
• Estimate the potential economic benefits from installing a wood-fired heating system
1.2 Evaluation Criteria, Project Scale, Operating Parameters, General Observations
• This project meets the Alaska Wood Energy Development Task Group objectives for
petroleum fuel displacement, use of hazardous forest fuels or forest treatment residues,
sustainability of the wood supply, project implementation, operation and maintenance, and
community support
• Using an estimate of 50,000 gallons per year, this project would be considered relatively
large in terms of its scale.
• Medium and large energy consumers have the best potential for feasibly implementing a
wood-fired heating system. Where preliminary feasibility assessments indicate positive
financial metrics, detailed engineering analyses are usually warranted.
• Cordwood systems are generally appropriate for applications where the maximum heating
demand ranges from 100,000 to 1,000,000 Btu per hour. “Bulk fuel” systems are generally
applicable for situations where the heating demand exceeds 1 million Btu per hour. How-
ever, these are general guidelines; local conditions can exert a strong influence on the best
system choice.
• Efficiency and emissions standards for Outdoor Wood Boilers (OWB) changed in 2006,
which could increase costs for small systems
1.3 Assessment Summary and Recommended Actions
• Overview. The Hoonah School heating system is housed in its own building directly
behind and in reasonably close proximity (100 feet) to the school. It consists of two
Kewanee oil-fired boilers rated at 2,050 MBH (net each). Currently, the installed nozzles
(2 per boiler) operate at a maximum rate of 5.5 gph (each). These boilers were installed in
1992, and reportedly are in good operational condition. However, the manufacturer is no
longer in business and repair parts, though still available, are becoming more difficult to
5
obtain. Domestic hot water for the school is provided by separate oil-fired water heaters
(number, manufacturer and specifications not noted).
The gym/pool boiler room is located within the gym/pool building, approximately 320 feet
from the school boiler building. The heating system consists of two Weil McLain H-486-
S-W oil fired boilers installed in 1982 (CP No. 775956). The boilers are IBR rated at 626.1
MBH (net, each). Although nearing the end of their service life expectancy, these boilers
appear to be in reasonably good condition and may be sufficient to serve as back-up boilers
to a wood-fired heating system. Domestic hot water is provided by a single 250 gallon,
PVI Industries “Copperglas” 9.0-G-250-A-O (SN 118454216) oil-fired water heater rated
at 1.2 MBH with a fuel oil input of 9.0 gph.
• Fuel Consumption. The Hoonah School building consumes approximately 30,000 gallons
of #2 fuel oil per year, and the gym/pool consumes approximately 20,000 gallons of fuel
oil per year.
• Potential Savings. With current fuel prices at $5.35 per gallon and total consumption of
50,000 gallons of fuel oil per year, the annual cost of fuel oil for the Hoonah School and
gym/pool is roughly $267,500. The HELE cordwood fuel equivalent of 50,000 gallons of
fuel oil is approximately 555 cords, and at $175/cord represents a potential annual fuel
cost savings of $170,375 (Debt service and OM&R costs notwithstanding). The bulk fuel
equivalent of 50,000 gallons of fuel oil is approximately 1,405 tons, and at $70/ton
represents a potential annual fuel cost savings of $169,150 (Debt service and OM&R costs
notwithstanding).
• Required boiler capacity. The estimated required boiler capacity (RBC) to heat the Hoonah
School and gym/pool during the coldest 24-hour period is undeterminable since a presumably
significant portion of the fuel is used to maintain consistent water temperatures in the
swimming pool. However, if all the fuel was used to provide space heat, the estimated
required boiler capacity (RBC) would be approximately 1.6 million Btu/hr during the coldest
24-hour period.
• Recommended action regarding a cordwood system. The financial metrics of installing
multiple large HELE cordwood boilers are strongly positive, with simple payback periods
between 5 and 6 years. Net present values are strongly positive and the internal rates of
return, at 20 years, range from about 12½ to 13½ percent. Formal consideration of a
HELE cordwood system for the Hoonah School/gym/pool is warranted. See Section 6.
• Recommended action regarding a bulk fuel wood system. A “bulk fuel” system appears
financially feasible for the Hoonah School/gym/pool, given a consistent and reasonably-
priced fuel supply and average initial investment costs. Formal consideration of a bulk fuel
system for the Hoonah School/gym/pool is warranted. See Section 7.
1.4 Power Generation and Waste Heat Capture
There are five diesel generators installed at the Hoonah School -- (2) 75 kW generators, (1)
100 kW generator, and (2) 150 kW generators. These generators are co-located with the
school boilers and water heaters. Apparently, none of these generators, individually, is
large enough to supply the school with all its electrical needs, and the electrical control
system is insufficiently designed to handle multiple generator operation/inputs. Therefore,
the system is not being used, except in emergencies. It is worth noting, however, that a
waste-heat reclamation system, tied into the oil-fired boilers, is already in place.
6
All electricity in Hoonah is currently diesel-generated, and the cost of self-generated power
would offer little or no savings over purchased power. However, given total electrical
consumption of approximately 500,000 kilowatt-hours per year, the potential to offset
heating costs with reclaimed waste heat is substantial. At $0.60 per kWh, the annual cost
of electricity amounts to approximately $300,000. Given that the school, pool, and gym
consume about 50,000 gallons of fuel oil per year for space heat, domestic hot water, and
pool water heating (at an annual cost of $250,000 to $275,000), it appears that the potential
savings could be significant. Anecdotally, this was demonstrated last winter during a one-
day power outage when one of the large generators was brought online. Apparently,
although 150 kW is less than the total amount of power required for optimal operation of
the school, it was enough to “get by”. Furthermore, the captured waste heat was more than
sufficient to keep the school warm; enough so that boilers did not have to fire at all.
If the power production/management issue(s) can be sufficiently resolved, and a waste heat
capture system utilized to its full capacity, any discussion of a wood-fired heating system
large enough to supply both the school and the gym/pool may be moot. Further
consideration by a qualified engineer is strongly recommended.
SECTION 2. EVALUATION CRITERIA, IMPLEMENTATION, WOOD HEATING SYSTEMS
The approach being taken by the Alaska Wood Energy Development Task Group (AWEDTG)
regarding biomass energy heating projects follows the recommendations of the Biomass Energy
Resource Center (BERC), which advises that, “[T]he most cost-effective approach to studying the
feasibility for a biomass energy project is to approach the study in stages.” Further, BERC advises
“not spending too much time, effort, or money on a full feasibility study before discovering whether
the potential project makes basic economic sense” and suggests, “[U]ndertaking a pre-feasibility
study . . . a basic assessment, not yet at the engineering level, to determine the project's apparent
cost-effectiveness”. Biomass Energy Resource Center, Montpelier, Vermont. www.biomasscenter.org
2.1 Evaluation Criteria
The Hoonah School and gym/pool project meets the AWEDTG criteria for potential petroleum fuel
displacement, use of forest residues for public benefit, use of local processing residues,
sustainability of the wood supply, project implementation, operation and maintenance, and
community support.
In the case of a cordwood boiler system, the combination of cordwood supplied from forest-derived
resources and local sawmill residues appears adequate, although more efficient processing and
production equipment would be desirable. The “bulk fuel” infrastructure is nearly non-existent;
apparently there is some processing equipment in town, but it is not installed. To supply bulk fuel
to the Hoonah School would entail developing that capability.
2.2 Successful Implementation
In general, four aspects of project implementation have been important to wood energy projects in
the past: 1) a project “champion”, 2) clear identification of a sponsoring agency/entity, 3) dedica-
tion of and commitment by facility personnel, and 4) a reliable and consistent supply of fuel.
In situations where several organizations are responsible for different community services, it must
be very clear which organization(s) would sponsor and/or implement a wood-burning project.
(NOTE: This is not necessarily the case with the Hoonah School, but the issue should be addressed
if germane.)
7
With manual systems, boiler stoking and/or maintenance is required for approximately 5-10
minutes per boiler several times a day (depending on the heating demand), and dedicating
personnel for the operation is critical to realizing savings from wood fuel use. Though automated,
bulk fuel systems also have a daily labor requirement. For this report, it is assumed that new
personnel would be hired or existing personnel would be assigned as necessary, and that “boiler
duties” would be included in the responsibilities and/or job description of facility personnel.
Another option would be to hire a local vendor/contractor to provide such services.
The forest industry infrastructure in/around Hoonah is not large, but appears to be sufficient to
supply the necessary wood requirements. Some local processing capabilities, whether for cordwood
or bulk fuel, would need to be developed, but the basic infrastructure is in place.
2.3 Classes of Wood Energy Systems
There are, essentially, two classes of wood energy systems: manual cordwood systems and
automated “bulk fuel” systems. Cordwood systems are generally appropriate for applications
where the maximum heating demand ranges from 100,000 to 1,000,000 Btu per hour, although
smaller and larger applications are possible. “Bulk fuel” systems are systems that burn wood chips,
sawdust, bark/hog fuel, shavings, pellets, etc. They are generally applicable for situations where the
heating demand exceeds 1 million Btu per hour, although local conditions, especially fuel
availability and cost, can exert strong influences on the feasibility of a bulk fuel system.
Usually, an automated bulk fuel boiler is tied-in directly with the existing oil-fired system. With a
cordwood system, glycol from the existing oil-fired boiler system would be circulated through a
heat exchanger at the wood boiler ahead of the existing oil boiler. A bulk fuel system is usually
designed to replace 100% of the fuel oil used in the oil-fired boiler, and although it is possible for a
cordwood system to be similarly designed, they are usually intended as a supplement, albeit a large
supplement, to an oil-fired system. In either case, the existing oil-fired system would normally
remain in place and be available for peak demand or backup in the event of downtime (scheduled
or unscheduled) in the wood system.
SECTION 3. THE NATURE OF WOOD FUELS
3.1 Wood Fuel Forms and Current Utilization
Currently, potential wood fuel supplies in Hoonah are fairly abundant. There is one fairly large,
full-time sawmill operation (Icy Straits Lumber & Milling), a small, full-time sawmill operation
(D&L Woodworks), and several part-time sawmill operations. Wood could come from a variety of
land ownerships, including Huna Totem Corp., Sealaska Corp., and the USDA Forest Service.
Wood fuels in Hoonah, currently, are most likely to be in the form of cordwood or large mill
residues (slabs, edgings) since there is no demand for bulk fuels locally. However, bulk fuels could
be produced if demand was sufficient to warrant the investment in the processing equipment.
3.2 Heating Value of Wood
Wood is a unique fuel whose heating value is quite variable, depending on species of wood,
moisture content, and other factors. There are also several ‘heating values’, namely high heating
value (HHV), gross heating value (GHV), recoverable heating value (RHV), and deliverable
heating value (DHV), that may be assigned to wood at various stages in the calculations.
8
For this report, hemlock cordwood at 30 percent moisture content (MC30) and hemlock bulk fuel
at 50 percent moisture content (MC50), calculated on the green wet weight basis (also called wet
weight basis), are used as benchmarks. NOTE: Drier wood will have greater heater value, and less
of it would be required to deliver a given amount of heat.
The HHV of hemlock at 0% moisture content (MC0) is 8,515 Btu/lb1. The GHV at 30% moisture
content (MC30) is 5,961 Btu/lb, and the GHV at 50% moisture content (MC50) is 4,258 Btu/lb.
The RHV for cordwood (MC30) is calculated at 13.26 million Btu per cord, and the DHV, which
is a function of boiler efficiency (assumed to be 75%), is 9.945 million Btu per cord. The delivered
heating value of 1 cord of hemlock cordwood (MC30) equals the delivered heating value of 90.08
gallons of #2 fuel oil when oil is burned at 80% efficiency and wood is burned at 75% efficiency.
The RHV for bulk fuel (MC50) is calculated at 5.61 million Btu per ton, and the DHV, which is a
function of boiler efficiency (assumed to be 70%), is 3.927 million Btu per ton. The delivered
heating value of 1 ton of hemlock bulk fuel (MC50) equals the delivered heating value of 35.57
gallons of #2 fuel oil when oil is burned at 80% efficiency and wood is burned at 70% efficiency.
A more thorough discussion of the heating value of wood can be found in Appendix B and
Appendix D.
SECTION 4. WOOD-FUELED HEATING SYSTEMS
4.1 Low Efficiency High Emission (LEHE) Cordwood Boilers
Most manual outdoor wood boilers (OWBs) that burn cordwood are relatively low-cost and can
save fuel oil but have been criticized for low efficiency and smoky operation. These could be called
low efficiency, high emission (LEHE) systems and there are dozens of manufacturers. In 2006, the
State of New York instituted a moratorium on new LEHE OWB installations due to concerns over
emissions and air quality5. Other states have also considered or implemented new regulations6,7,8,9.
Since there are no standards for OWBs (“boilers” and “furnaces” were exempt from the 1988 EPA
regulations10), OWB ratings are inconsistent and can be misleading. Prior to 2006, standard
procedures for evaluating wood boilers did not exist, but test data from New York, Michigan and
elsewhere showed a wide range of apparent [in]efficiencies and emissions among OWBs.
In 2006, a committee was formed under the American Society for Testing and Materials (ASTM)
to develop a standard test protocol for OWBs11. The standards included uniform procedures for
determining performance and emissions. Subsequently, the ASTM committee sponsored tests of
three common outdoor wood boilers using the new procedures. The results showed efficiencies as
low as 25% and emissions more than nine times the standard for other industrial boilers.
Obviously, these results were deemed unsatisfactory and new OWB standards were called for.
In a news release dated January 29, 200712, the U.S. Environmental Protection Agency announced
a new voluntary partnership agreement with 10 major OWB manufacturers to make cleaner-
burning appliances. The new phase-one standard calls for emissions not to exceed 0.60 pounds of
particulate emissions per million Btu of heat input. The phase-two standard, which will follow 2
years after phase-one, will limit emissions to 0.30 pounds per million Btus of heat delivered,
thereby creating an efficiency standard as well.
To address local and state concerns over regulating OWB installations, the Northeast States for
Coordinated Air Use Management (NeSCAUM), and EPA have developed model regulations that
9
recommend OWB installation specifications, clean fuel standards and owner/operator training.
(http://www.epa.gov/woodheaters/ and http://www.nescaum.org/topics/outdoor-hydronic-heaters)
Implementation of the new standard will improve air quality and boiler efficiency but will also
increase costs as manufacturers modify their designs, fabrication and marketing to adjust to the
new standards. Some low-end models will no longer be available.
4.2 High Efficiency Low Emission (HELE) Cordwood Boilers
In contrast to low efficiency, high emission cordwood boilers there are a few units that can be
considered high efficiency, low emission (HELE). These systems are designed to burn cordwood
fuel cleanly and efficiently, mostly by incorporating some degree of gasification technology.
Table 4-1 lists three HELE boiler suppliers, all of which have units operating in Alaska.
BioHeatUSA (formerly TarmUSA) and Greenwood and have a number of residential units
operating in Alaska. A number of Garn boilers, manufactured by Dectra Corporation, have been
installed in larger institutional applications in Dot Lake, Tanana and Kasilof; several others are in
the planning stages.
Table 4-1. HELE Cordwood Boiler Suppliers
Supplier Btu/hr ratings Brands
Bio Heat USA
www.bioheatusa.com 100,000 to 198,000 Tarm, Scandtec, Froling
Greenwood
www.greenwoodusa.com 100,000 to 300,000 Greenwood
Dectra Corp.
www.garn.com 350,000 to 950,000 Garn
Note: Listing of any manufacturer, distributor or service provider does not constitute an endorsement.
Table 4-2 shows the test results for a high efficiency boiler (Garn WHS 1350) that was tested at
157,000 to 173,000 Btu per hour using standardized testing procedures, compared with EPA
standards for wood stoves and boilers. It is important to remember that wood fired boilers are not
entirely smokeless; even very efficient wood boilers may smoke for a few minutes on startup.4,15
Table 4-2. Emissions from Wood Heating Appliances
Appliance Emissions
(grams/1,000 Btu delivered)
EPA Certified Non Catalytic Stove 0.500
EPA Certified Catalytic Stove 0.250
EPA Industrial Boiler (many states) 0.225
Garn WHS 1350 Boiler* 0.179
Source: Intertek Testing Services, Michigan, March 2006.
Note: *With dry oak cordwood; average efficiency of 75.4% based upon the high heating value (HHV) of wood
Other gasification-style wood boiler manufacturers and/or suppliers include Econoburn, Wood
Gun, TurboBurn, and EKO-Line. (And there may be others.) However, there are no known
10
operating units by these suppliers in Alaska, and it is unknown whether any of the appliances sold
by these suppliers meet the efficiency or emission standards discussed in Section 4.1.
4.3 Bulk Fuel Boiler Systems
Commercial bulk fuel systems are generally efficient and meet typical federal and state air quality
standards. They have been around for a long time and there is little new technological ground to
break when installing one. Efficient bulk fuel boilers typically convert 70% of the energy in the
wood fuel to hot water or low pressure steam when the fuel moisture is less than 40% moisture
content (MC40, calculated on a wet basis). NOTE: It is possible to incorporate fuel dryers when
dealing with wetter feedstocks.
Most vendors provide systems that can burn various bulk fuels (wood chips, sawdust, wood pellets,
hog fuel, etc.), but each system, generally, has to be designed around the predominant fuel form. A
system designed to burn clean sawmill chips will not necessarily operate well on a diet of hog fuel,
for example. And most vendors will emphasize the need for good quality wood fuel as well as a
consistent source, i.e., fuel of consistent size and moisture content from a common source is
considerably more desirable than variations in chip size and/or moisture content from numerous
suppliers. Table 4-3 presents a partial list of bulk fuel boiler system vendors.
Table 4-3. Bulk Fuel Boiler System Vendors
Decton Iron Works, Inc
www.decton.com
New Horizon Corp.
www.newhorizoncorp.com
Messersmith Manufacturing, Inc.
www.burnchips.com
Precision Energy Services, Inc
www.pes-world.com
Chiptec Wood Energy Systems
www.chiptec.com
Bio-Fuel Technologies
www.bio-fueltechnologies.com
Note: Listing of any manufacturer, distributor or service provider does not constitute an endorsement
Bulk fuel systems are available in a range of sizes between 300,000 and 60,000,000 Btu/hr.
However, the majority of the institutional installations range from 1 MMBtu/hr to 20 MMBtu/hr.
Larger energy consumers, consuming at least 35,000 gallons of fuel oil per year, have the best
potential for installing bulk fuel boilers and may warrant detailed engineering analysis. Bulk fuel
systems with their storage and automated fuel handling conveyances are generally not cost-
effective for smaller applications.
Although there are several options, bulk fuel is best delivered in 40-ft, self-unloading, tractor-
trailer vans that hold about 22 tons of material. A facility such as the Hoonah School/gym/pool,
replacing 50,000 gallons of fuel oil with hemlock bulk fuel (MC50), would use an estimated 1,405
tons per year, or about 2 tractor-trailer loads per week (on average) throughout the school year.
There are four known bulk fuel boilers in Alaska (Table 4-4), three of which are installed at
sawmills. The most recent was installed in Craig in 2008 and consists of a 4 MMBtu/hr wood chip
gasifier at the Craig Aquatic Center and School. It is designed to replace the equivalent of 36,000
gallons of fuel oil per year, and is similar in size to boilers recently installed in several Montana
schools. Bulk fuel boilers are also being considered for school heating projects in Delta Junction,
Tok and Haines. Bulk fuel systems are discussed in more detail in Section 7.
11
Table 4-4. Bulk Fuel Boilers in Alaska
Installation Boiler
Horsepower* MMBtu/hr Heating
Degree Days** Supplier
Craig Aquatic Center
Craig, AK 120 4 7,209a Chiptek
Icy Straits Lumber & Milling
Hoonah, AK 72 2.4 8,496b Decton
Regal Enterprises
Copper Center, AK N/A N/A 13,486c Decton
Logging & Milling Associates
Delta Junction, AK N/A 2 12,897d Decton
Table 4-4 Notes:
* Heat delivered as hot water or steam. 1 Boiler Horsepower = 33,475 Btu/hr or 34.5 pounds of water at a temperature of
100°C (212°F) into steam at 212°F
** assumes base temperature = 65o F
a NOAA, July 1, 2005 through June 30, 2006, Ketchikan data
b NOAA, July 1, 2005 through June 30, 2006, Average of Juneau and Yakutat data
c NOAA, July 1, 2005 through June 30, 2006, Gulkana data
d NOAA, July 1, 2005 through June 30, 2006, Big Delta data
ftp://ftp.cpc.ncep.noaa.gov/htdocs/products/analysis_monitoring/cdus/degree_days/archives/Heating%20degree%20Days/Monthly%20City/2006/jun%202006.txt
SECTION 5. SELECTING THE APPROPRIATE SYSTEM
Selecting the appropriate heating system is, primarily, a function of heating demand. It is generally
not feasible to install automated bulk fuel systems in/at small facilities, and it is likely to be
impractical to install cordwood boilers at very large facilities. Other than demand, system choice
can be limited by fuel availability, fuel form, labor, financial resources, and limitations of the site.
The selection of a wood-fueled heating system has an impact on fuel economy. Potential savings
in fuel costs must be weighed against initial investment costs and ongoing operating, maintenance
and repair (OM&R) costs. Wood system costs include the initial capital costs of purchasing and
installing the equipment, non-capital costs (engineering, permitting, etc.), the cost of the fuel
storage building and boiler building (if required), the financial burden associated with loan interest,
the fuel cost, and the other costs associated with operating and maintaining the heating system,
especially labor.
5.1 Comparative Costs of Fuels
Table 5-1 (next page) compares the cost of #2 fuel oil to hemlock cordwood (MC30) and hemlock
bulk fuel (MC50). In order to make reasonable comparisons, costs are provided on a “per million
Btu” (MMBtu) basis.
12
Table 5-1. Comparative Cost of Fuel Oil vs. Wood Fuels
FUEL RHVa
(Btu)
Conversion
Efficiencya
DHVa
(Btu)
Price per unit
($)
Cost per MMBtu
(delivered, ($))
5.00/gallon 45.29
5.50 49.819 Fuel oil, #2,
(per 1 gallon) 138,000 80% 110,400
6.00 54.348
175/cord 17.597
200 20.111 Hemlock,
(per 1 cord, MC30)
13.26
million 75% 9.945
million 225 22.624
70/ton 17.825
80 20.372 Hemlock
(per 1 ton, MC50)
5.61
million 70% 3.927
million 90 22.918
Notes:
a from Appendix D
5.2(a) Cost per MMBtu Sensitivity – Cordwood
Figure 5-1 (next page) illustrates the relationship between the price of hemlock cordwood (MC30)
and the cost of delivered heat, (the slanted line). For each $25 per cord increase in the price of
cordwood, the cost per million Btu increases by about $2.514. The chart assumes that the
cordwood boiler delivers 75% of the RHV energy in the cordwood to useful heat and that oil is
converted to heat at 80% efficiency. The dashed lines represent fuel oil at $5.00, $5.50 and $6.00
per gallon ($45.29, $49.819 and $54.348 per million Btu respectively).
At high efficiency, heat from hemlock cordwood (MC30) at $481.93 per cord is equal to the
current cost of oil at $5.35 per gallon ($48.46/MMBtu), before considering the cost of the
equipment and operation, maintenance and repair (OM&R) costs. At 75% efficiency and $175 per
cord, a high-efficiency cordwood boiler will deliver heat at about 36.3% of the current cost of fuel
oil ($17.597 versus $48.46 per MMBtu respectively). Figure 5-1 indicates that, at a given
efficiency, savings increase significantly with decreases in the delivered price of cordwood and/or
with increases in the price of fuel oil.
13
Cost ($) per MMBtu as a Function of
Cordwood Cost
0.000
10.000
20.000
30.000
40.000
50.000
60.000
150 200 250 300 350 400 450 500 550
Cordwood cost, $ per cordCost ($) per MMBtu
Fuel Oil at $6.00 per gallon
Fuel Oil at $5.50 per gallon
Fuel Oil at $5.00 per gallon
Figure 5-1. Effect of Hemlock Cordwood (MC30) Price on Cost of Delivered Heat
5.2(b) Cost per MMBtu Sensitivity – Bulk Fuels
Figure 5-2 (next page) illustrates the relationship between the price of hemlock bulk fuel (MC50)
and the cost of delivered heat, (the slanted line). For each $10 per ton increase in the price of bulk
fuel, the cost per million Btu increases by about $2.55. The chart assumes that the bulk fuel boiler
converts 70% of the RHV energy in the wood to useful heat and that fuel oil is converted to heat at
80% efficiency. The dashed lines represent fuel oil at $5.00, $5.50 and $6.00 per gallon ($45.29,
$49.819 and $54.348 per million Btu respectively).
At standard efficiency, heat from hemlock bulk fuel (MC50) at $190.30 per ton is equal to the
current cost of oil at $5.35 per gallon ($48.46/MMBtu), before considering the investment and
OM&R costs. At 70% efficiency and $70/ton, a bulk fuel boiler will deliver heat at about 36.8% of
the cost of fuel oil at $5.35 per gallon ($17.825 versus $48.46 per MMBtu respectively). Figure
5-2 shows that, at a given efficiency, savings increase significantly with decreases in the delivered
price of bulk fuel and/or with increases in the price of fuel oil.
14
Cost ($) per MMBtu as a Function of
Bulk Fuel Cost
0.000
10.000
20.000
30.000
40.000
50.000
60.000
50 75 100 125 150 175 200
Bulk fuel cost, $ per tonCost ($) per MMBtu
Fuel Oil at $6.00 per gallon
Fuel Oil at $5.50 per gallon
Fuel Oil at $5.50 per gallon
Figure 5-2. Effect of Hemlock Bulk Fuel (MC50) Price on Cost of Delivered Heat
5.3 Determining Demand
Table 5-2 shows the reported approximate amount of fuel oil used by the Hoonah School, gym and
pool.
Table 5-2. Reported Annual Fuel Oil Consumption, Hoonah School and Gym/pool
Reported Annual Fuel Consumption Facility Gallons Cost ($) @ $5.35/gallon
Gym/pool 20,000 107,000
Hoonah School 30,000 160,500
Total 50,000 267,500
Wood boilers, especially cordwood boilers, are often sized to displace only a portion of the heating
load since the oil system typically remains in place, in standby mode, for “shoulder seasons” and
peak demand. Fuel oil consumption for the Hoonah School and gym/pool was compared with
heating demand based on heating degree days (HDD) to determine the required boiler capacity
15
(RBC) for heating only on the coldest 24-hour day (Table 5-3). While there are many factors to
consider when sizing heating systems it is clear that, in most cases, a wood system of less-than-
maximum size could still replace a substantial quantity of fuel oil.
NOTE: In the gym/pool building, much of the heat is used to maintain the pool water temperature,
not for space heating. However, the calculations in Table 5-3 were made as if all the fuel oil was
used for space heating.
Typically, installed oil-fired heating capacity at most sites is two to four times the demand for the
coldest day. The installed capacity at the school is slightly greater than four times the estimated
RBC and the installed capacity at the pool/gym is about 1.9 times the estimated RBC.
Manual HELE cordwood boilers, equipped with special tanks for extra thermal storage, can supply
heat at higher than their rated capacity for short periods. For example, while rated at 950,000
Btu/hr (heat into storage*), a trio of Garn® WHS 3200 boilers can store more than 6 million Btu,
which would be enough to heat the Hoonah School during the coldest 24-hour period for more than
6 hours (6,192,000 ÷ 970,396).
Table 5-3. Estimate of Heat Required in Coldest 24 Hr Period
Facility Fuel Oil Used
gal/yeara
Heating
Degree Daysd Btu/DDc Design
Tempd F
RBCe
Btu/hr
Installed
Btu/hra
Gym/pool 20,000 242,504 647,057 1,252,200
Hoonah School 30,000 363,756 970,396 4,100,000
Total 50,000
9,105
(Juneau data)
606,260
1
(Juneau data)
1,617,073 5,352,200
Table 3-7 Notes:
a From SOI and site visit; net Btu/hr
b NOAA, July 1, 2005 through June 30, 2006:
ftp://ftp.cpc.ncep.noaa.gov/htdocs/products/analysis_monitoring/cdus/degree_days/archives/Heating%20degree%20Days/Monthly%20City/2006/jun%202006.txt
c Btu/DD= Btu/year x oil furnace conversion efficiency (0.85) /Degree Days
d Alaska Housing Manual, 4th Edition Appendix D: Climate Data for Alaska Cities, Research and Rural Development
Division, Alaska Housing Finance Corporation, 4300 Boniface Parkway, Anchorage, AK 99504, January 2000.
e RBC = Required Boiler Capacity for the coldest Day, Btu/hr= [Btu/DD x (65 F-Design Temp)+DD]/24 hrs
* Btu/hr into storage is fuel dependent. The data provided for Garn boilers by Dectra Corp. is based on the
ASTM standard of split, 16-inch oak with 20 percent moisture content and reloading once an hour.
5.4 Summary of Findings Table 5-4 summarizes the findings thus far: annual fuel oil usage, range of annual fuel oil costs, estimated annual wood fuel requirement, range of estimated annual wood fuel costs, and potential gross annual savings for the Hoonah School and gym/pool. [Note: potential gross annual fuel cost savings do not consider capital costs and non-fuel operation, maintenance and repair (OM&R) costs.] Table 5-4. Estimate of Total Wood Consumption, Comparative Costs and Potential Savings Annual Fuel Oil Cost (@ $ ___ /gal) HOONAH SCHOOL and GYM/POOL Fuel Oil Used gal/yeara 5.00 5.50 6.00 Approximate Wood Requirementb Annual Wood Cost (@ $ ___ /unit) Potential Gross Annual Fuel Cost Savings ($) W. Hemlock, MC30, CE 75% 175/cord 200/cord 225/cord Low Medium High Cordwood system 555 cords 97,125 111,000 124,875 125,125 164,000 202,875 W. Hemlock, MC50, CE 70% 70/ton 80/ton 90/ton Low Medium High Bulk fuel system 50,000 250,000 275.000 300,000 1,405 tons 98,350 112,400 126,450 123,550 162,600 201,650 NOTES: a From Table 5-2 b From Table D-3, Fuel Oil Equivalents
SECTION 6. ECONOMIC FEASIBILITY OF CORDWOOD SYSTEMS
6.1 Initial Investment Cost Estimates
DISCLAIMER: Short of having an actual Design & Engineering Report prepared by a team of
architects and/or engineers, actual costs for any particular system at any particular site cannot be
positively determined. Such a report is beyond the scope of this preliminary assessment. However,
several hypothetical systems are offered as a means of comparison. Actual costs, assumptions and
“guess-timates” are identified as such, where appropriate. Recalculations of financial metrics, given
different/updated cost estimates, are readily accomplished.
Wood heating systems include the cost of the fuel storage building (if necessary), boiler building
(if necessary), boiler equipment (and shipping), plumbing and electrical connections (including
plumbing, heat exchangers and electrical service to integrate with existing distribution systems),
installation, and an allowance for contingencies.
Before a true economic analysis can be performed, all of the costs (investment and OM&R) must
be identified, and this is where the services of qualified experts are necessary.
Table 6-1 (next page) presents hypothetical scenarios of initial investment costs for several
cordwood systems in a large heating demand situation. Three alternatives are presented.
Building(s) and plumbing/connections are the most significant costs besides the boiler(s). Building
costs deserve more site-specific investigation and often need to be minimized to the extent
possible. Piping from the wood-fired boiler is another area of potential cost saving. Long
plumbing runs and additional heat exchangers substantially increase project costs. The high cost of
hard copper and/or iron pipe normally used in Alaska now precludes its use in nearly all
applications. If plastic or PEX® piping is used significant cost savings may be possible.
Allowances for indirect non-capital costs such as engineering and contingency are most important
for large systems that involve extensive permitting and budget approval by public agencies. This
can increase the cost of a project by 25% to 50%. For the examples in Table 6-1, a 25%
contingency allowance was used.
NOTES:
a. With the exception of the list prices for Garn boilers, all of the figures in Table 6-1 are
estimates.
b. The cost estimates presented in Table 6-1 do not include the cost(s) of any upgrades or
improvements to the existing heating/heat distribution system currently in place.
c. These examples are based on the assumption that all current fuel oil use is used for space
heating, which is NOT the actual case. Some of the fuel oil is used to heat pool water or
domestic hot water, which may require a different set of calculations that are beyond the
scope of this report. Consultation with a qualified engineer is required.
18
Table 6-1. Initial Investment Cost Scenarios for Hypothetical Cordwood Systems
Fuel oil consumption
(gallons per year)
20,000
(Gym/pool only)
30,000
(School only)
50,000
(Gym/pool + School)
Required boiler capacity (RBC),
Btu/hr 647,057f 970,396 1,617,073f
Garn model Cordwood boiler
Btu/hre
(2) WHS 3200
1,900,000
(3) WHS 3200
2,850,000
(5) WHS 3200
4,750,000
Building and Equipment (B&E) Costs (for discussion purposes only)
Fuel storage buildinga
(fabric bldg, gravel pad, $20 per sf)
$88,800
(222 cords; 4,440 sq ft)
$133,200
(333 cords; 6,660 sq ft)
$222,000
(555 cords; 11,100 sq ft)
Boiler building @ $150 per sf
(minimum footprint w/concrete pad)b
$60,000
(20’ x 20’)
$90,000
(30’ x 20’)
$150,000
(50’ x 20’)
Boilers
Base pricec
Shippingd
$70,000
$8,000
$105,000
$12,000
$175,000
$20,000
Plumbing/connectionsd $60,000 $70,000 $130,000
Installationd $30,000 $35,000 $65,000
Subtotal - B&E Costs 316,800 445,200 762,000
Contingency (25%)d 79,200 111,300 190,500
Grand Total 396,000 556,500 952,500
Notes:
a A cord occupies 128 cubic feet. If the wood is stacked 6½ feet high, the area required to store the wood is 20 square feet per cord.
b Does not allow for any fuel storage within the boiler building
c List price, Alaskan Heat Technologies
d “guess-timate”; for illustrative purposes only
e Btu/hr into storage is extremely fuel dependent. The data provided for Garn boilers by Dectra Corp. are based on the ASTM standard of split, 16-inch oak
with 20 percent moisture content and reloading once an hour.
f Assumes all fuel oil used is used to provide space heat, which is NOT the actual case; a significant though undetermined portion is used to maintain pool water
temperatures and some is used for domestic hot water
6.2 Operating Parameters of HELE Cordwood Boilers
A detailed discussion of the operating parameters of HELE cordwood boilers can be found in
Appendix F.
6.3 Hypothetical OM&R Cost Estimates
The primary operating cost of a cordwood boiler, other than the cost of fuel, is labor. Labor is
required to move fuel from its storage area to the boiler building, fire the boiler, clean the boiler
and dispose of ash. For purposes of this analysis, it is assumed that the boiler system will be
operated 210 days (30 weeks) per year between mid-September and mid-April.
Table 6-2 (next page) presents labor/cost estimates for various HELE cordwood systems. A
detailed analysis of labor requirement estimates can be found in Appendix F.
19
Table 6-2. Labor/Cost Estimates for HELE Cordwood Systems
Facility Hoonah School and Gym/Pool
System (Garn Model) (2) WHS 3200
(Gym/pool only)
(3) WHS 3200
(School only)
(5) WHS 3200
(Gym/pool + School)
Total Daily labor (hrs/yr)
(hrs/day X 210 days/yr) 248.06 385.11 659.23
Total Periodic labor (hrs/yr)
(hrs/wk X 30 wks/yr) 222 333 555
Total Annual labor (hrs/yr) 40 60 100
Total labor (hrs/yr) 510.06 778.11 1,314.23
Total annual labor cost ($/yr)
(total hrs x $20) $10,201.20 $15,562.20 $26,284.60
Source: Appendix F, Tables F-2 and F-3
There is also an electrical cost component to the boiler operation. An electric fan creates the
induced draft that contributes to boiler efficiency. The cost of operating circulation pumps and/or
blowers would be about the same as it would be with the oil-fired boiler or furnaces in the existing
heating system.
Lastly, there is the cost of maintenance and repair items, such as fire brick, door gaskets, water
treatment chemicals, etc. For this exercise, a flat rate of $1,000 per boiler per year is used. The non-
fuel OM&R cost estimates are summarized in Table 6-3.
Table 6-3. Summary of Total Annual Non-Fuel OM&R Cost Estimates
Cost/Allowance ($)
Item (2) WHS 3200
(Gym/pool only)
(3) WHS 3200
(School only)
(5) WHS 3200
(Gym/pool + School)
Labor 10,201 15,562 26,285
Electricity 1,187 1,781 2,986
Maintenance/Repairs 2,000 3,000 5,000
Total non-fuel OM&R ($) $13,388 $20,343 $34,271
Notes for Table 6-3: a From Table 6-2
b Electrical cost based on a formula of horsepower x kWh rate x operating time. Assumed kWh rate = $0.60
6.4 Calculation of Financial Metrics
Biomass heating projects are viable when, over the long run, the annual fuel cost savings generated
by converting to biomass are greater than the cost of the new biomass boiler system plus the
20
additional operation, maintenance and repair (OM&R) costs associated with a biomass boiler
(compared to those of a fossil fuel boiler or furnace).
Converting from an existing boiler to a wood biomass boiler (or retrofitting/integrating a biomass
boiler with an existing boiler system) requires a greater initial investment and higher annual
OM&R costs than for an equivalent oil or gas system alone. However, in a viable project, the
savings in fuel costs (wood vs. fossil fuel) will pay for the initial investment and cover the
additional OM&R costs in a relatively short period of time. After the initial investment is paid off,
the project continues to save money (avoided fuel cost) for the life of the boiler. Since inflation
rates for fossil fuels are typically higher than inflation rates for wood fuel, increasing inflation rates
result in greater fuel cost savings and thus greater project viability.17
The potential financial viability of a given project depends not only on the relative costs and cost
savings, but also on the financial objectives and expectations of the facility owner. For this reason,
the impact of selected factors on potential project viability is presented using the following metrics:
Simple Payback Period
Present Value (PV)
Net Present Value (NPV)
Internal Rate of Return (IRR)
Total initial investment costs include all of the capital and non-capital costs required to design,
purchase, construct and install a biomass boiler system in an existing facility with an existing
furnace or boiler system.
A more detailed discussion of Simple Payback Period, Present Value, Net Present Value and
Internal Rate of Return can be found in Appendix E.
6.5 Simple Payback Period for Multiple HELE Cordwood Boilers
Table 6-4 presents a Simple Payback Period analysis for hypothetical multiple HELE cordwood
boiler installations.
Table 6-4. Simple Payback Period Analysis for HELE Cordwood Boilers
(2) WHS 3200
(Gym/pool only)
(3) WHS 3200
(School only)
(5) WHS 3200
(Gym/pool + School)
Fuel oil cost
($ per year @ $5.35 per gallon)
107,000
(20,000 gal)
160,500
(30,000 gal)
267,500
(50,000 gal)
Cordwood cost
($ per year @ $175 per cord)
38,850
(222 cds)
58,275
(333 cds)
97,125
(555 cds)
Annual Fuel Cost Savings ($) 68,150 102,225 170,375
Total Investment Costs ($)b 396,000 556,500 952,500
Simple Payback (yrs)c 5.81 5.44 5.59
Notes:
a From Table 6-3
b From Table 6-1
c Total Investment Costs divided by Annual Fuel Cost Savings
21
6.6 Present Value (PV), Net Present Value (NPV) and Internal Rate or Return (IRR)
Values for Multiple HELE Cordwood Boilers
Table 6-5 presents PV, NPV and IRR values for hypothetical multiple HELE cordwood boiler
installations.
Table 6-5. PV, NPV and IRR Values for Multiple HELE Cordwood Boilers
(2) WHS 3200
(Gym/pool only)
(3) WHS 3200
(School only)
(5) WHS 3200
(Gym/pool + School)
Discount Ratea (%) 3
Time, “t”, (years) 20
Initial Investment ($)b 396,000 556,500 952,500
Annual Cash Flow ($)c 54,762 81,882 136,104
Present Value
(of expected cash flows, $ at “t” years) 814,720 1,218,197 2,024,884
Net Present Value ($ at “t” years) 418,720 661,697 1,072,384
Internal Rate of Return (% at “t” years) 12.52 13.56 13.06
See Note # _ below 1 2 3
Notes:
a real discount (excluding general price inflation) as set forth by US Department of Energy, as found in NIST publication NISTIR 85-3273-22, Energy
Price Indices and Discount Factors for Life Cycle Cost Analysis – April 2007
b From Table 6-1
c Equals annual cost of fuel oil minus annual cost of wood minus annual non-fuel OM&R costs (i.e. Net Annual Savings)
Note #1. With a real discount rate of 3.00% and after a span of 20 years, the projected cash flows are worth
$814,720 today (PV), which is greater than the initial investment of $396,000. The resulting NPV of the
project is $418,720 and the project achieves an internal rate of return of 12.52% at the end of 20 years. Given
the assumptions and cost estimates, this alternative appears to be economically and operationally feasible.
Note #2. With a real discount rate of 3.00% and after a span of 20 years, the projected cash flows are worth
$1,218,197 today (PV), which is greater than the initial investment of $556,500. The resulting NPV of the
project is $661,697 and the project achieves an internal rate of return of 13.56% at the end of 20 years. Given
the assumptions and cost estimates, this alternative appears to be economically and operationally feasible.
Note #3. With a real discount rate of 3.00% and after a span of 20 years, the projected cash flows are worth
$2,024,884 today (PV), which is greater than the initial investment of $952,500. The resulting NPV of the
project is $1,072,384 and the project achieves an internal rate of return of 13.06% at the end of 20 years. Given
the assumptions and cost estimates, this alternative appears to be economically and operationally feasible.
6.7 The Case for Fuel Purchase Planning and Fuel Storage
Too often, a fuel storage building is omitted from a project in order to save the initial investment cost
and improve the cost-effectiveness of the project. This is FALSE ECONOMY. The importance of a
fuel storage building cannot be stressed enough, especially in southeast Alaska. With good planning,
fuel could be purchased a year or more in advance and be given sufficient time to dry, while incurring
no additional cost. And a fuel storage building can pay for itself in less time than the boiler!
22
Protected from the elements and provided with good air circulation, it is not unreasonable to expect
split and well-stacked cordwood to achieve moisture contents in the neighborhood of fiber saturation
point (approximately 23% on the wet weight basis) or less. The difference in heating value between
hemlock cordwood at MC30 (partially air-dried) and hemlock cordwood at MC23 (well air-dried) is
notable – about 13 percent more recoverable heat value (RHV) in the drier wood, which amounts to
about 1,700,000 Btu per cord. And instead of a cord replacing 90.05 gallons of #2 fuel oil, a cord
could now replace 101.5 gallons.
For the Hoonah school, gym and pool, this would mean that instead of having to buy 555 cords per
year, that fuel requirement becomes 493 cords, a savings of 62 cords and $10,850 per year (at $175
per cord). NOTE: There are also operational cost savings that can be realized due to fewer boiler
stokings, less ash removal/disposal, and less fuel handling.
The opposite is also true. Cordwood left exposed to the elements in southeast Alaska will not dry
much at all and may, in fact, gain moisture. The difference in total RHV Btu value between a cord of
hemlock at MC30 (partially air-dried) and a cord of hemlock at MC50 (“green”) is more than 4.84
million Btu. The wetter wood has roughly 63.5% of the heating value of the drier wood. In terms of
its #2 fuel oil equivalence, the value is 57.16 gallons per cord at MC50 compared to 90.05 gallons per
cord at MC30.
For the Hoonah school, gym and pool, this would mean that instead of having to buy 555 cords
(MC30) per year, that cordwood equivalent becomes 875 cords (“dead green”), an increase of 320
cords and $56,000 per year (at $175 per cord). NOTE: There are also operational cost increases that
would have to be incurred due to more frequent boiler stokings, more ash removal/disposal, and
additional fuel handling.
In summary:
875 cords of green wood per year at $175 = $153,125 versus 493 cords of well air-dried wood per
year at $175 = $86,275. The savings between green wood and well dried wood would be
$66,850/year. Given a fuel storage building costing $277,500 ($220,000 plus 25% contingency as
shown in Table 6-1), the simple payback would be about 4.15 years.
6.8 Life Cycle Cost Analysis
The National Institute of Standards and Technology (NIST) Handbook 135, 1995 edition, defines
Life Cycle Cost (LCC) as “the total discounted dollar cost of owning, operating, maintaining, and
disposing of a building or a building system” over a period of time. Life Cycle Cost Analysis
(LCCA) is an economic evaluation technique that determines the total cost of owning and
operating a facility over a period of time. Alaska Statute 14.11.013 directs the Department of
Education and Early Development (EED) to review school capital projects to ensure they are in the
best interest of the state, and AS 14.11.014 stipulates the development of criteria to achieve cost
effective school construction.19
While a full-blown life cycle cost analysis is beyond the scope of this preliminary feasibility
assessment, an attempt is made to address some of the major items and run a rudimentary LCCA
using the Alaska EED LCCA Handbook and spreadsheet.
According to the EED LCCA Handbook, the life cycle cost equation can be broken down into three
variables: the costs of ownership, the period of time over which the costs are incurred
(recommended period is 20 years), and the discount rate that is applied to future costs to equate
them to present costs.
23
There are two major costs of ownership categories: initial expenses and future expenses. Initial
expenses are all costs incurred prior to occupation (or use) of a facility, and future expenses are all
costs incurred upon occupation (or use) of a facility. Future expenses are further categorized as
operation costs, maintenance and repair costs, replacement costs, and residual value. A
comprehensive list of items in each of these categories is included in the EED LCCA Handbook.
The discount rate is defined as, “the rate of interest reflecting the investor’s time value of money”,
or, the interest rate that would make an investor indifferent as to whether s/he received payment
now or a greater payment at some time in the future. NIST takes the definition a step further by
separating it into two types: real discount rates and nominal discount rates. The real discount rate
excludes the rate of inflation and the nominal discount rate includes the rate of inflation.19 The
EED LCCA Handbook and spreadsheet focuses on the use of real discount rates in the LCC
analysis.
To establish a standard discount rate for use in the LCCA, EED adopted the US Department of
Energy’s (DOE) real discount rate. This rate is updated and published annually in the Energy Price
Indices and Discount Factors for Life Cycle Cost Analysis – Annual Supplement to NIST
Handbook 135 (www1.eere.energy.gov). The DOE discount and inflation rates for 2008 are as
follows:
Real rate (excluding general price inflation) 3.0%
Nominal rate (including general price inflation) 4.9%
Implied long term average rate of inflation 1.8%
Other LCCA terms
Constant dollars: dollars of uniform purchasing power tied to a reference year and exclusive of
general price inflation or deflation
Current dollars: dollars of non-uniform purchasing power, including general price inflation or
deflation, in which actual prices are stated
Present value: the time equivalent value of past, present or future cash flows as of the beginning of
the base year.
NOTE: When using the real discount rate in present value calculations, costs must be expressed in
constant dollars. When using the nominal discount rate in present value calculations, costs must be
expressed in current dollars. In practice, the use of constant dollars simplifies LCCA, and any
change in the value of money over time will be accounted for by the real discount rate.
LCCA Assumptions
As stated earlier, it is beyond the scope of this pre-feasibility assessment to go into a detailed life
cycle cost analysis. However, a limited LCCA is presented here for purposes of discussion and
comparison.
Time is assumed to be 20 years, as recommended by EED
The real discount rate is 3%
Initial expenses as per Table 6.1
Future expenses as per Table 6.3
Replacement costs – not addressed
Residual value – not addressed
24
Cordwood Boiler Alternatives
Alternative 1 represents the existing oil-fired boiler systems. The initial investment was assumed
to be $100,000. The operation costs included 50,000 gallons of #2 fuel oil at $5.35 per gallon and
40 hours of labor per year at $20 per hour. The annual maintenance and repairs costs were
assumed to be $2,000 and no allowances were made for replacement costs or residual value.
NOTE: The value of the existing boiler system ($100,000), the amount and cost of labor (40 hours,
$800), and maintenance and repair costs ($2,000) are fictitious, but are held constant for
comparative purposes as appropriate.
Alternative 2 represents the existing oil-fired boiler systems, which would remain in place, plus the
installation of five Garn WHS 3200 wood fired boilers. The initial investment was assumed to be
$1,052,500, which includes the hypothetical value of the existing oil-fired boilers (valued at
$100,000 as per Alternative 1) plus the initial investment cost of the Garn boiler system ($952,500,
as per Table 6-1). The operation costs include 555 cords of fuelwood at $175 per cord and
1,314.23 hours of labor per year at $20 per hour (as per Table 6-2). The annual utility,
maintenance and repair costs were assumed to be $7,986 (as per Table 6-3) for the system and no
allowances were made for replacement costs or residual value.
The hypothetical EED LCCA results for the Hoonah School/gym/pool cordwood boiler alternative
are presented in Table 6-6.
Table 6-6. Estimated Life Cycle Costs of Cordwood System Alternative
Alternative 1
(existing boilers)
Alternative 2
(existing boilers plus HELE
cordwood boilers)
Initial Investment Cost $100,000 $1,002,500
Operations Cost $3,991,627 $1,836,023
Maintenance & Repair Cost $29,755 $118,812
Replacement Cost $0 $0
Residual Value $0 $0
Total Life Cycle Cost $4,121,381 $2,957,335
SECTION 7. ECONOMIC FEASIBILITY OF BULK FUEL SYSTEMS
A typical bulk fuel boiler system includes bulk fuel storage, boiler building, wood-fuel handling
systems, combustion chamber, boiler, ash removal, cyclone, exhaust stack and electronic controls.
The variables in this list of system components include the use of silos or bunkers of various sizes
for wood fuel storage, chip storage areas of various sizes, boiler buildings of various configura-
tions, automated versus manual ash removal and cyclones for particulate removal (if necessary).17
7.1 Capital Cost Components
As indicated, bulk fuel systems are larger, more complex and often more costly to install and
integrate with existing boiler and distribution systems. Before a true economic analysis can be
25
performed, all of the costs (capital, non-capital and OM&R) must be identified, and this is where
the services of architects and civil and mechanical engineers are necessary.
Table 7-1 outlines the various general components for a hypothetical, small bulk fuel system;
however it is beyond the scope of this report to offer estimates of actual costs for those
components. As an alternative, a range of likely total costs is presented and analyzed for
comparative purposes.
Table 7-1. Initial Investment Cost Components for Bulk Fuel Systems
Facility Hoonah school, gym and pool
(50,000 gallons/year; 1,405 tons/year, (MC50))
Capital Costs: Building and Equipment (B&E)
Fuel storage building ?
Material handling system ?
Boiler building ?
Boiler: base price
shipping ?
Plumbing/connections ?
Electrical systems ?
Installation ?
Non-capital Costs
Engineering , Permitting, Contingency, etc.?
Initial Investment Total ($) $1,000,000 to $2,000,000
The investment cost of bulk fuel systems installed in institutional settings can range from $500,000
to over $2 million, with about $350,000 to $900,000 in equipment costs. Fuel handling and boiler
equipment for an 8 MMBtu/hr (300 BHP) system was recently quoted to a school in the northeast
USA for $900,000. The cost of a boiler and fuel handling equipment for a 3 to 4 MMBtu/hr system
is about $350,000 to $500,000. The 2.4 MMBtu/hr system in Hoonah was installed at a sawmill
for around $250,000, but an existing building was used and there were significant economies in
fuel preparation and fuel handling that would be unacceptable in a non-industrial, setting. Fuel and
boiler equipment for a 1 MMBtu per hour system is estimated at $250,000 to $300,000 (buildings
are extra). Several schools in New England have been able to use existing buildings or boiler
rooms to house new equipment and realize substantial savings, but recent school projects in
Montana were all installed in new buildings.4
The cost of a bulk fuel heating system at the Craig School and Aquatic Center in Craig, AK was
originally estimated at less than $1 million, designed to replace propane and fuel oil equivalent to
36,000 gallons of fuel oil. But the results of a January 2007 bid opening brought the cost to $1.85
million. The fuel storage and boiler building, fuel dryer, and system integration costs for the pool
and two schools increased the project costs. NOTE: The City of Craig undertook construction of
the project using a “force account” and brought the final cost down to about $1.5 million.
26
Table 7-2 shows the total costs (in 2005) for the Darby School (Darby, MT) project at $1,001,000
including $268,000 for repairs and upgrades to the pre-existing heating system. Integration with any pre-
existing system will likely require repairs and rework that must be included in the wood system cost.
Adding the indirect costs of engineering, permits, etc. to the equipment cost put the total cost at Darby
between $716,000 and $766,000 for the 3 million Btu/hr system to replace 47,000 gallons of fuel oil per
year. Since the boiler was installed at Darby, building and equipment costs have increased from 10% to
25% (as of 2007). A new budget price for the Darby system might be closer to $800,000 excluding the
cost of repairs to the existing system.4
Table 7-2. Darby, MT Public School Wood Chip Boiler Costs a
Boiler Capacity 3 MMBtu/hr
Fuel Oil Displaced 47,000 gallons
Heating Degree Days 7,186
System Costs:
Building, Fuel Handling $ 230,500
Boiler and Stack $ 285,500
Boiler system subtotal $ 516,000
Piping, integration $ 95,000
Other repairs, improvements $ 268,000
Total, Direct Costs $ 879,000
Engineering, permits, indirect $ 122,000
Total Cost $1,001,000
a Biomass Energy Resource Center, 2005 4
The following is an excerpt from the Montana Biomass Boiler Market Assessment17:
“To date, CTA [CTA Architects and Engineers, Billings, MT] has evaluated more than 200
buildings throughout the northwestern United States and designed 13 biomass boiler projects, six of
which are now operational. Selected characteristics of these projects, including total project cost,
are presented in Table 1 [7-3]. As can be seen from Table 1 [7-3], total costs for these projects do
not correlate directly with boiler size. The least expensive biomass projects completed to date cost
$455,000 (not including additional equipment and site improvements made by the school district)
for a wood chip system in Thompson Falls, Montana. The least expensive wood pellet system is
projected to cost $269,000 in Burns, Oregon. The general breakdown of costs for these two projects
is presented in Tables 2 [7-4] and 3.”
NOTE: Information related to wood pellet systems was not included in this report as wood
pellets are not readily available as a fuel in southeast Alaska.
27
Table 7-3. Characteristics of Biomass Boiler Projects17
Facility
Name Location Boiler Size
(MMBtu/hr output) Project Type
Wood
Fuel
Type
Total
Project
Cost
Thompson
Falls School
District
Thompson
Falls, MT 1.6 MMBtu Stand-alone boiler building
tied to existing steam system Chips $ 455,000
Glacier High
School
Kalispell,
MT 7 MMBtu
New facility with integrated
wood chip and natural gas
hot water system
Chips $ 480,000
Victor School
District Victor, MT 2.6 MMBtu Stand-alone boiler building
tied to existing steam system Chips $ 615,000
Philipsburg
School District
Philipsburg,
MT 3.87 MMBtu
Stand-alone boiler building
tied to existing hot water
system
Chips $ 684,000
Darby School
District Darby, MT 3 MMBtu
Stand-alone boiler building
tied to existing steam & hot
water system
Chips $1,001,000
City of Craig Craig, AK 4 MMBtu
Stand-alone boiler building
tied to existing hot water
systems
Chips $1,500,000
Univ. MT
Western Dillon, MT 14 MMBtu Addition to existing steam
system Chips $1,400,000
Table 7-4. Cost Breakdown for the Least Expensive Wood Chip Boiler System Installed in a
New Free-Standing Building 17
System Component Cost % of Total
Wood Boiler System Equipment $136,000 30%
Building $170,000 38%
Mechanical/Electrical $100,000 22%
Mechanical Integration $15,000 3%
Fees, Permits, Printing, Etc. $34,000 7%
Total* $455,000* 100%
* not including additional equipment and site improvements made by the school district
7.2 Generic OM&R Cost Allowances
The primary operating cost is fuel. The estimated bulk fuel cost for the Hoonah school, gym and
pool is $98,350 (1,405 tons @ $70/ton). Other O&M costs would include labor, electricity, and
maintenance and repair costs. For purposes of this analysis, it is assumed that the boiler will
operate daily, 210 days (30 weeks) per year, from mid-September through mid-April.
Daily labor would consist of monitoring the system and performing daily inspections as prescribed
by the system manufacturer. It is assumed that the average daily labor requirement is ½ hour. An
additional 2 hours per week is allocated to perform routine maintenance tasks. Therefore, the total
annual labor requirement estimate is (210 x 0.5) + 60 = 165 hours per year. At $20 per hour, the
annual labor cost would be $3,300.
28
There is also an electrical cost component to the boiler operation. Typically, electrically-powered
conveyors of various sorts are used to move fuel from its place of storage to a metering bin and into
the boiler. There are also numerous other electrical systems that operate various pumps, fans, etc.
The Darby High School system in Darby, MT, which burned 755 tons of bulk fuel in 2005, used
electricity in the amount of $2,035,18 however the actual kWh or cost per kWh were not reported.
Another report17 proffered an average electricity cost for Montana of $0.086 per kWh. If that rate
is true for Darby, then the electrical consumption would have been about 23,663 kWh. The
Hoonah school, gym and pool system is projected to use 1,405 tons of bulk fuel (1.86 times the
amount used at Darby). If it is valid to apportion the electrical usage based on bulk fuel
consumption, then the Hoonah school, gym and pool system would use about 44,013 kWh per year.
At $0.60 per kWh, the annual electric bill would be $26,408.
Lastly, there is the cost of maintenance and repair. Bulk fuel systems with their conveyors, fans,
bearings, motors, etc. have more wear parts. An arbitrary allowance of $5,000 is made to cover
these costs.
Total annual operating, maintenance and repair cost estimates for a bulk fuel boiler at the Hoonah
school, gym and pool are summarized in Table 7-5
Table 7-5. Total OM&R Cost Allowances for a Bulk Fuel System
Item Cost/Allowance
Non-Fuel OM&R
Labor ($) 3,300
Electricity ($) 26,408
Maintenance ($) 5,000
Total, non-fuel OM&R 34,708
Wood fuel ($) 98,350
Total OM&R ($) 133,058
7.3 Calculation of Financial Metrics
A discussion of Simple Payback Period can be found in Appendix E.
A discussion of Present Value can be found in Appendix E.
A discussion of Net Present Value can be found in Appendix E.
A discussion of Internal Rate of Return can be found in Appendix E.
7.4 Simple Payback Period for Generic Bulk Fuel Boilers
Table 7-6 (next page) presents Simple Payback Period analysis for a range of initial investment
cost estimates for generic bulk fuel boiler systems.
29
Table 7-6. Simple Payback Period Analysis for Bulk Fuel Heating Systems
Hoonah school, gym and pool
(50,000 gpy; 1,405 tons/yr)
Fuel oil cost
($ per year @ $5.35 per gallon 267,500
Bulk wood fuel
($ per year @ $70 per ton) 98,350
Annual Fuel Cost Savings ($) 169,150
Total Investment Costs ($) 750,000 1,000,000 1,250,000 1,500,000 1,750,000 2,000,000
Simple Payback (yrs)a 4.43 5.91 7.39 8.87 10.34 11.82
a Simple Payback equals Total Investment Costs divided by Annual Fuel Cost Savings
While simple payback has its limitations in terms of project evaluations, one of the conclusions of
the Montana Biomass Boiler Market Assessment was that viable projects had simple payback
periods of 10 years or less.17
7.5 Present Value (PV), Net Present Value (NPV) and Internal Rate of Return (IRR)
Values for a Hypothetical Bulk Fuel Boiler Installed at the Hoonah school/gym/pool
Table 7-7 presents PV, NPV and IRR values for hypothetical bulk fuel boilers.
Table 7-7. PV, NPV and IRR Values for Bulk Fuel Systems
Discount Rate 3
Time, “t”, (years) 20
Initial Investment ($)a 750,000 1,000,000 1,250,000 1,500,000 1,750,000 2,000,000
Annual Cash Flow ($)b 134,442
Present Value (of expected cash
flows), ($ at “t” years) 2,000,157
Net Present Value ($ at “t” years) 1,250,157 1,000,157 750,157 500,157 250,157 157
Internal Rate of Return (%) 17.17 12.07 8.74 6.34 4.49 3.00
Notes:
a from Table 7-6
b Equals annual cost of fuel oil minus annual cost of wood minus annual non-fuel OM&R costs
30
SECTION 8. CONCLUSIONS
This report discusses conditions found “on the ground” at the Hoonah school, gym and pool in
Hoonah, Alaska, and attempts to demonstrate, by use of realistic, though hypothetical examples,
the feasibility of installing high efficiency low emission cordwood and/or bulk fuel wood boilers
for heating these facilities.
Wood is a viable heating fuel in a wide range of institutional applications, however, below a certain
minimum and above a certain maximum, it may be impractical to heat with wood, or it may require
a different form of wood fuel and/or heating system. The difference in the cost of heat derived
from wood versus the cost of heat derived from fuel oil is significant, as illustrated in Table 5-1. It
is this difference in the cost of heat, resulting in monetary savings that must “pay” for the
substantially higher investment and OM&R costs associated with wood fuel systems.
The Hoonah school, gym and pool, taken together, can be considered “large” in terms of their total
fuel oil consumption (50,000 gpy). It appears possible to heat these buildings (and pool),
separately or together, with a cordwood heating system. Taken as a single project, it may be large
enough to justify the installation of a bulk fuel wood heating system if investment costs can be
controlled and a reliable consistent fuel supply identified.
The topography around the school, gym and pool is hilly, but there is a level area behind the school
(currently serving as a ball field and playground) that would be suitable for either a cordwood or
bulk fuel biomass heating system. Delivery trucks can access the site, perhaps with some slight
difficulty, and the proximity of the site to the buildings to be heated is reasonable. It may even be
possible/feasible to tie-in the police department building and fire hall, which are up the street.
8.1 Cordwood Systems
To replace 50,000 gallons of #2 fuel oil per year would require approximately 555 cords of
reasonably dry (MC30) hemlock cordwood or large sawmill residues.
Examples of installing and operating multiple, large cordwood boilers are presented in Section 6.
In order to supply enough heat for both the school and the gym/pool, a total of five large HELE
boilers would have to be installed. And in order to consume 555 cords of wood per year those
boilers would require an average of 3.7 firings per day (See Appendix F). If provisions are made to
capture waste heat from the diesel generators to heat the school, a cordwood boiler system
consisting of two large boilers would be necessary to provide heat to the gym/pool. And even
though this would be a much smaller system, this option still appears quite cost-effective.
Initial investment costs for the installation of multiple cordwood boilers ranged from about
$396,000 (for the gym/pool alone) to $952,000 (for the combined school + gym/pool), with the
cost of the fuel storage building being the single most costly item ($111,000 to $278,000).
However, each boiler installation scenario returned positive financial metrics with simple payback
periods ranging from 5.44 to 5.81 years, and internal rates of return ranging from 12.52 to 13.56
percent.
8.2 Bulk Fuel System
To replace 50,000 gallons of fuel oil per year would require approximately 1,405 tons
(approximately sixty-four 40-foot tractor trailer loads) of bulk fuel (chips, sawdust, bark, shavings,
etc.), assuming such fuel runs 50% moisture content (MC50).
31
Although it is beyond the scope of this assessment to delve into the detailed costs associated with
the installation of bulk fuel systems, it is not unrealistic to say that, at 50,000 gallons of fuel oil per
year, it appears quite likely that a bulk fuel system could be cost-effective for the Hoonah
school/gym/pool IF:
1. a reliable, consistent source of fuel can be identified
2. fuel can be delivered at a reasonable cost
3. total investment costs can be held to less than $2,000,000
If provisions are made to capture waste heat from the diesel generators to heat the school, then a
bulk fuel boiler system would probably not be cost-effective for heating the gym/pool given the
considerably smaller heating load (i.e., 20,000 gpy). A cordwood system would then be the better
option.