Loading...
HomeMy WebLinkAboutEmmonak Alakanuk Wind Turbines 2016-WEmmonak, Alaska Emmonak School participates in Wind for Schools program Quick Facts Total Project Costs: $8.9 million Funding: Renewable Energy Fund & Local Match Capital Costs Design: $24,235 Construction: $8,867,392 Equipment Specifications Make/Model: (4) Northern Power 100B Rated Capacity: 100 kW Net Capacity Factor: 17.7% Rotor Diameter: 21 meters Hub Height: 37 meters Total Rated Capacity: 400 kW Diesel Fuel Offset Estimated Annual: 55,785 gallons Actual Annual: 35,000 gallons Sept. 2011-Dec. 2014: 111,000 gallons Fuel Savings Estimated Annual: $205,017 Actual Annual: $136,000 Sept. 2011-Dec. 2014: $435,000 Emmonak/Alakanuk Wind Turbines Project Overview In partnership with the Alaska Energy Authori- ty (AEA), the Alaska Village Electric Cooperative (AVEC) completed the final design and construction of a wind project to provide power to the communi- ties of Emmonak and Alakanuk. Four 100 kW North- wind turbines were installed in additon to a 9.5 mile, 160-pole transmission line from Emmonak to Alaka- nuk. Objectives The main objectives of this project were to displace expensive diesel fuel and provide Emmonak and Alakanuk with a renewable, reliable, and cost effective energy source. Economic Feasibility The project became operational in September of 2011. Between September of 2011 and December of 2014, it generated 1,560 Megawatt hours of electricity and displaced 111,000 gallons of diesel fuel. This displace- ment saved the communities $435,000 in just over three years. Over its 20-year projected lifespan, the project has a calculated benefit/cost ratio of .99. Project Specifications The four 100 kW turbines were provided by Northern Power. They have a design life of over 20 years and an operating temperature between -40 degrees F to +122 degrees F. Winter temperatures in Emmonak and Alakanuk typically range from -35 to +25 degrees F, so the turbines have no trouble operating during the coldest months. Wind energy is classified on a scale from 1 to 7, 1 being poor and 7 being superb. Emmonak is a high Class 3 for power generation. The 9.5-mile transmission line connects the communities Emmonak School, photo courtesy of Skweskimos.com of Emmonak and Alakanuk so that they can share the harnessed energy. Allocation of Funding The Alaska Energy Authority’s Renewable Energy Fund (REF) granted $8 million for the project’s design and construction. Local funds contributed $891,627 which were used for the same project phases. Learning Experiences/Challenges Although originally proposed as a $10.7 million proj- ect, the scope changed with the $4 million cap applied to each community for a total REF grant of $8 million. The scope was reduced from 6 to 4 turbines and the transmission line increased to 9.5 miles due to better ground and barge access. Like much of northern Alaska, Emmonak and Alaka- nuk are located on permafrost zones. Construction crews took this into account by engineering 60-foot steel pilings with a prefabricated concrete sectional cap on each turbine’s foundation. These were engineered to isolate the turbine from the permafrost and damp- en vibrations. This was a necessary innovation to deal with unique geotechnical and logistical conditions. Community Benefits Electricity costs from diesel average about $0.50/kWh, compared with $0.21/kWh with wind energy. This savings is important for the schools especially, which use substantial electricity for lighting and heating during the school year. Both Emmonak and Alakanuk are subject to subzero temperatures, extended periods of darkness, blowing snow, and other factors that make electricity and heat essential.This project also provides excess energy for water heating at the school and water plant. Emmonak School was one of five Alaska schools cho- sen to participate in the 2014 spring Wind for Schools (WfS) program. The Renewable Energy Alaska Project brought the WfS curriculum to classes. During their visit they facilitated WfS activities with teachers and students, provided the school with a wind experiment kit, and brought in real wind data so that students could see how the wind turbines contribute to their community’s overall energy production. Using wind energy as a keystone, students learn about energy science, energy sources, climate change, physics, and mathematics. Project Contact Information Parties Involved: Kirstin Enanoria, AVEC Email: kenanoria@avec.org Case Study Author: Zoe Tressel, AEA Website: Akenergyauthority.org Phone: 907-771-3000 Emmonak, Alaska Northern Power 100 turbines, photo courtesy of AEA. Northern Power Tur- bines, photo courtesy of Solsticeak.com Published August, 2015